| XG25KTR-3M | XG30KTR | XG33KTR | XG36KTR | XG40KTR | |
| Input (DC) | |||||
| Max. Input Power | 40kW | 48kW | 52.8kW | 57.6kW | 64kW |
| Max. Input Voltage | 1100V | ||||
| Start Voltage / Min. Operating Voltage | 250V / 200V | ||||
| MPPT Voltage Range | 200V ~ 1000V | ||||
| Number of MPP Trackers / String per MPPT | 3 / 2 | 4 / 2 | |||
| Max. Current per MPPT | 26A | 26A | |||
| Output (AC) | |||||
| Max. Output Current | 40.1A | 48.3A | 53A | 57.8A | 64.3A |
| Rated Output Power | 25kW | 30kW | 33kW | 36kW | 40kW |
| Max. Output Power | 27.5kVA | 33kVA | 36.3kVA | 39.6kVA | 44kVA |
| Rated Grid Frequency | 50Hz / 60Hz | ||||
| Rated Grid Voltage | 230V / 400V, 3L+N+PE / 3L+PE | ||||
| Power Factor | -0.8 ~ +0.8 (adjustable) | ||||
| THDi | < 3% (at rated power) | ||||
| Efficiency | |||||
| Max. Efficiency | 98.60% | ||||
| European Efficiency | 98.40% | ||||
| MPPT Efficiency | 99.90% | ||||
| Protection | |||||
| Protection | DC switch, Input over voltage protection, AC short circuit protection, AC over current protection, Isolation protection, PV string protection, DC ARC fault protection, RCD protection, Surge protection, Anti-islanding protection, Over temperature protection, Grouding fault monitoring, Grid monitoring, Single/Multiple inverter anti-reverse protection etc. | ||||
| Communication | |||||
| Display | LED / LCD / WiFi+App | ||||
| Communication | standard: RS485 / USB optional: WiFi / GPRS / Ethernet | ||||
| Standard Compliance | |||||
| Grid Connection Standards | IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N 4110:2018, VDE-AR-N 4105:2018, VDE-AR-N 4120:2018, EN 50549, AS/NZS 4777.2:2015, CEI 0-21, VDE 0126-1-1/A1 VFR 2014, UTE C15-712-1:2013, DEWA DRRG, NRS 097-2-1, MEA/PEA, C10/11, G98/G99 | ||||
| Safety / EMC | IEC 62109-1:2010, IEC 62109-2:2011, EN 61000-6-2:2005, EN 61000-6-3:2007/A1:2011 | ||||
| General parameter | |||||
| Dimensions (W x H x D) | 570 x 420 x 230 mm | ||||
| Weight | 32kg | ||||
| Operating Temperature Range | -30℃ ~ +60℃ (derating above 45℃) | ||||
| Cooling Method | Smart Cooling | ||||
| Protection Degree | IP66 | ||||
| Max. Operating Altitude | ≤4000m (derating above 3000m) | ||||
| Relative Humidity | 0 ~ 100% | ||||
| Topology | Transformerless | ||||
| Night Power Consumption | <1W | ||||
| Warranty | 5 years (standard) / 10 years (optional) | ||||